Earth fault monitoring

Detect differences. Report immediately.

Earth fault monitoring

Measures and compares the 50 Hz components at three inputs.

The earth fault monitor measures the 50 Hz components of the applied AC voltages, compares them and shows them on an LC display.

If a differential voltage exceeds the adjustable reference, the fault LED and relay are set for the duration of the fault and the fault is shown on the display.

Features

  • 3 inputs
  • 8th-order SC Butterworth filter
  • Measuring range 100 or 1,000 V
  • 2 changeover outputs
  • 3-line LC display

Applications

Voltage comparison

Compares the 50 Hz components at three inputs and reports impermissible differences immediately via relay and LED.

Testing without a fault

In test mode you set a test voltage per channel and check the tripping.

Specifications

Operating voltage
100–240 V AC, 0.15 A, 50/60 Hz
Inputs
3
Input resistance
3.6 MΩ
Measuring filter
50 Hz, 3.7 % bandwidth
Filter type
8th-order SC Butterworth filter
Measuring range
100 or 1,000 V (jumper)
Rejection of other frequencies
60 dB at > 150 Hz
Outputs
2 changeover contacts, 60 V, 0.5 A
Display
3-line, 16-character LC display

Subject to change. Full details in the data sheet – Request data sheet

Frequently asked questions

How do I test the tripping?

In test mode you set a test voltage for each measuring channel. Test operation is indicated by a flashing LED.

How do I know the device is ready?

A green LED lights up, and a separate relay monitors the operating voltages – it stays closed as long as the device is ready.

Which measuring ranges are available?

100 V or 1,000 V, selectable with a jumper.

Documents

We send data sheets, operating manuals, software and firmware by e-mail on request.

You might also be interested in

SLE-TeleGraph

See, save and understand measurements.

Interested in earth fault monitoring?

We are happy to advise you and prepare a quote.