Knowledge

Monitoring capacitors.

Why capacitor banks in ripple control coupling units and absorption circuits fail – and how capacitor protection detects faults before consequential damage occurs.

Where capacitors work in ripple control

A ripple control transmitter feeds its audio-frequency signal into the network via a coupling unit. Capacitors and reactors let the audio frequency pass and keep the 50 Hz mains voltage away from the transmitter. Absorption circuits – combinations of capacitor and reactor tuned to one frequency – divert currents of that frequency in a targeted way.

In both cases, large capacitor banks are in operation, often at the high-voltage level. If one of them fails unnoticed, not only is the function impaired – the entire installation is at risk of damage.

Why capacitors fail

Typical faults are winding short circuits and winding interruptions inside the capacitors. They change the capacitance of the affected bank. With winding short circuits, the housing can bulge due to gas formation and eventually rupture.

Today’s PCB-free capacitors contain silicone-based impregnants and are relatively flammable. This makes it all the more important to detect a fault early and switch the installation off quickly and safely.

The principle: bridge circuit

Capacitor protection compares the capacitor banks of one phase in a bridge circuit. If all banks are intact, the bridge is balanced. If the capacitance of one bank changes, an asymmetry arises – the bridge voltage rises.

The circuit is sensitive: even a 1 % deviation in one bank changes the bridge voltage in a 110 kV installation by around 177 V. Because the measurement selectively processes the 50 Hz signal, ripple control transmissions do not distort the result.

Principle of the bridge circuit: intact and with a changed capacitor bankUBMeasuring moduleC1C2C3C4All banks intactBridge balanced: UB ≈ 0UBMeasuring moduleC1 changede.g. winding shortC2C3C4One bank changedAsymmetry: UB rises
Principle, simplified: the capacitor banks of one phase form a bridge. As long as all banks are equal, the bridge voltage UB is almost zero. If the capacitance of one bank changes, an asymmetry arises and UB rises – even a 1 % deviation changes it by around 177 V in a 110 kV installation.

Structure of a capacitor protection system.

  1. Measuring modules

    Mounted on the high-voltage level, self-supporting on the connection bolts. They capture the bridge voltage and are powered via a current transformer from the operating current of the installation – from 8 A, without a battery.

  2. Transmission

    The measured values travel by radio or infrared from the high-voltage level to the receivers – without a conductive connection.

  3. Central unit

    The KoSchutz2 central unit evaluates the values of all three phases, compares them with the set limits and switches the signalling outputs.

Structure of a capacitor protection system from measuring module to trippingHigh-voltage levelMeasuring module L1captures the bridge voltageMeasuring module L2captures the bridge voltageMeasuring module L3captures the bridge voltagePowered via current transformer,from 8 A, no batteryRadio orinfraredno conductiveconnectionReceiversRadio: communication modulepolls the modulesInfrared: one receiverper transmitterRS485Central unitKoSchutz2evaluates all threephases and comparesthem with the limitslogs to theSD cardSignalling outputs8 relays controlthe installation’sprotection, whichperforms thetripping
Simplified, with one measuring module per phase: the measured values travel from the high-voltage level to the receivers without a conductive connection and on to the central unit via RS485. Tripping is performed by the installation’s protection.

Radio or infrared.

Radio (KoSchutz Funk)

Transmission in the 433 or 868 MHz ISM band, licence- and fee-free. A communication module polls the measuring modules in turn and passes the values to the central unit via RS485. Range at least 10 m. KoSchutz Funk

Infrared (KoSchutz IR)

Optical transmission, 38 kHz modulated, Manchester-coded and secured with a CRC checksum. There is one receiver per transmitter; the receivers are connected to the central unit via RS485. KoSchutz IR

Both variants work with the KoSchutz2 central unit. We will be happy to work out together which one suits your installation better.

Signalling and tripping

For each channel, four switching thresholds can be freely programmed in the central unit; window values can be set independently for all three phases. If a threshold is exceeded, the central unit switches the corresponding signalling outputs – eight relays that also report faults such as a transmitter failure. Signalling delay and hysteresis are adjustable.

Measured values and messages are logged as CSV on the SD card and can be displayed as a trend over time – making gradual changes visible. For safety reasons, the central unit and display use separate microcontrollers: if the display fails, monitoring continues.

The actual tripping is performed by the installation’s protection, controlled via the signalling outputs.

Existing installations

Since 2024, the KoSchutz2 central unit has been housed in a new wall-mounted enclosure with almost the same dimensions as the previous one. An existing central unit can therefore be replaced without modifying the installation space. Radio and IR receivers can be fitted with a display showing measured values, signal strength and error messages directly at the receiver; existing installations can partly be retrofitted. KoSchutz Display

On request, our technicians commission the installation together with you – from setting up the central unit to testing the transmitting and receiving units. Capacitor protection

Frequently asked questions.

What is capacitor protection?

Monitoring of the capacitor banks in ripple control coupling units and absorption circuits. A bridge circuit detects asymmetries caused by winding short circuits or interruptions and signals them so that the installation can be switched off before consequential damage occurs.

Which installations is capacitor protection intended for?

For capacitor banks in ripple control coupling units and absorption circuits, for example at the 110 kV level – in existing and new installations.

How early does the monitoring detect a fault?

Even a 1 % deviation in one capacitor bank changes the bridge voltage significantly – by around 177 V in a 110 kV installation. Winding short circuits and interruptions are therefore noticed early.

Do ripple control transmissions interfere with the measurement?

No. The measurement selectively processes the 50 Hz signal, so ripple control transmissions do not distort the monitoring.

Do the measuring modules need batteries?

No. They are powered via a current transformer from the operating current of the installation – from 8 A.

Can I replace an existing central unit?

Yes. The wall-mounted housing of the KoSchutz2 introduced in 2024 has almost the same dimensions as the previous one – it can be replaced without modifying the installation space.

More terms are explained in the glossary. More articles: Measuring ripple control signals and Evaluating ripple control telegrams.

Discuss your installation.

Tell us about your coupling unit or absorption circuit – we will advise you on monitoring, replacement and commissioning.