Knowledge
Measuring ripple control signals.
Practical basics: how ripple control signals get into the network, what interferes with reception and how to measure the level reliably.
What is audio-frequency ripple control?
With audio-frequency ripple control, network operators send switching commands over the existing power grid – to many receivers at once and without additional lines. A ripple control transmitter in the substation superimposes an audio-frequency signal on the 50 Hz mains voltage; the coupling unit feeds it into the medium- or high-voltage level.
Ripple control receivers at customer premises or in installations recognise the telegrams and execute the commands – for example for tariff switching, storage heaters, heat pumps or street lighting.
Frequency, level and telegram
The ripple control frequency is usually in the range of a few hundred hertz. It is chosen to lie between the harmonics of the mains frequency – not at 250 Hz or 350 Hz, for example, where the 5th and 7th harmonics occur.
The ripple control level is the magnitude of the superimposed audio-frequency voltage, usually given as a percentage of the mains voltage. It is small compared with the mains voltage.
A telegram is a sequence of audio-frequency pulses in a defined time pattern. From the start pulse and the position of the following pulses, the receiver recognises which command is meant. The time pattern depends on the telegram method used.
Why the level varies across the network
On its way from the substation to the receiver, the signal changes. Line lengths, transformers and connected loads affect the audio frequency differently from 50 Hz.
- Capacitors – for example for reactive power compensation – present a low impedance to the audio frequency and can absorb the signal locally.
- Filters and absorption circuits tuned to neighbouring frequencies can also divert part of the signal.
- Converters and inverters introduce their own interference voltages and can attenuate the signal with their input filters.
- Resonances can, conversely, raise the level locally.
This is why a measurement at the substation is not enough: what matters is the level where the receivers are installed.
Typical faults.
Receivers do not switch, or only sporadically
The most common cause is a ripple control level that is too low at the installation point – for example at the end of long lines or behind installations that absorb the signal. Distorted or shortened pulses can also prevent a telegram from being recognised.
Receivers switch incorrectly or unintentionally
Interference voltages close to the ripple control frequency – for example from converters or other non-linear loads – can simulate or mask pulses.
Level is too high
Resonances between lines, transformers and capacitors can raise the signal locally. This can interfere with equipment on the network.
Damage to the coupling unit
Coupling units and absorption circuits contain large capacitor banks. Winding short circuits or interruptions change the capacitance – if they go unnoticed, consequential damage can result. Capacitor protection
How to measure.
- Clarify the frequency
Ask the network operator for the ripple control frequency and transmission times. Without the correct frequency, a selective instrument measures past the signal.
- Choose the measuring point
Measure where the problem occurs – at the socket, in the meter cabinet or in the local substation – and, for comparison, at a point where receivers switch reliably.
- Measure during a transmission
Capture the level of the start pulse selectively, on all three phases if necessary. Compare the result with the response threshold of the receivers.
- Record the telegram
The recording shows whether all pulses arrive complete, long enough and in the right position.
- Narrow down the cause
A frequency scan and the distortion factor reveal sources of interference. Current clamps help to trace where the audio-frequency current flows.
- Measure long-term and document
Sporadic faults often only show up over several days. A data logger records every transmission with a time stamp; the report serves as evidence.
Safety: Measurements on live installations may only be carried out by qualified electricians with suitable equipment – for example safety sockets and leads of the appropriate measurement category.
Selective rather than broadband
A broadband measurement captures everything present on the network – above all the 230 V mains voltage. The ripple control signal can hardly be seen in it.
A selective measurement uses a narrow-band filter to extract only the ripple control frequency. This allows the level to be determined precisely even alongside the much larger mains voltage. Our level meters offer selectable filter bandwidths of 1.7 %, 3.7 % and 6.0 %: narrow for clean separation from neighbouring interference frequencies, wider for a faster response to short pulses.
For permanent monitoring, there are measuring filters for fixed installation: they measure the level of every start pulse and pass it on to the control system as a current or voltage signal. Measuring filters
Which device for which task.
- Capture start pulse and pulse lengths
- SPM3A
- Several channels at once, e.g. three phases with current and voltage
- TF-Recorder
- Monitor the level permanently, value to the control system
- Measuring filters
- Test ripple control receivers
- RCR2s test bench
- Monitor coupling capacitors
- KoSchutz2
- Evaluate and document
- SLE-TeleGraph
Not sure what suits your measurement task? Go to the product finder
Frequently asked questions.
How high does the ripple control level have to be?
That depends on the response threshold of the receivers used and the network operator’s specifications. What matters is a sufficient margin above the response threshold at every installation point.
Can I measure the level with an ordinary multimeter?
No. A multimeter measures broadband and essentially shows the 50 Hz mains voltage. The ripple control signal, only a few volts, is lost in it – that requires selective measurement.
When should I measure?
During a ripple control transmission. For sporadic faults, a long-term recording over several days is recommended so that infrequent transmissions are captured as well.
Can I rent a measuring device?
Yes, many of our portable devices are available for rent – for example for commissioning or measurement campaigns. Rental units
More terms are explained in the glossary. More articles: Evaluating ripple control telegrams and Monitoring capacitors.